Skip to download

Dataset · datasheet versus field · FAST 2007

Disk replacement rates and fleet event gaps: reported values

An 18-row extraction of reported replacement rates and fleet event gaps, with source qualifiers and population limits; not a disk-lifetime dataset.

Download CSV18 rows · 7 columns · CSV

File /data/datasets/mttf-vs-field-replacement-rates.csv · JSON metadata · All datasets · Human-readable note on hesela.com

Method

The CSV transcribes figures printed in the text and tables of Schroeder and Gibson (FAST 2007), plus three cross-check figures from Pinheiro et al. (FAST 2007) and the Backblaze Q2 2026 Drive Stats post. It does not read chart values and it does not refit any distribution. The annual replacement rate (ARR) is drives replaced per year as a percent of drives in use. The datasheet AFR is power-on hours per year divided by MTTF.

Measurement clocks

The HPC1 interarrival results describe cluster replacement gaps, not individual disk lifetimes. Keep the event stream explicit: interarrival time, annual replacement rate and rate of occurrence of failures are distinct from a surviving device's lifetime hazard.

Limits

Table

18 rows, matching the CSV. Columns retain reported values or bounds, not necessarily confidence intervals. A blank means not stated, never zero. Read each source qualifier in the Note column before interpreting a value. Sources accessed 2026-10-09.

Reported measurements
MeasureReported lowerReported value / upperUnitScopeNoteCitation
datasheet AFR at MTTF 1000000 hoursnot stated0.88percent of drives per yearVendor datasheet arithmetic: power-on hours per year divided by MTTFSchroeder and Gibson print 0.88% for the 1000000 hour end of the range.schroeder-usenix-html
datasheet AFR at MTTF 1500000 hoursnot stated0.58percent of drives per yearVendor datasheet arithmetic: power-on hours per year divided by MTTFSchroeder and Gibson print 0.58% for the 1500000 hour end of the range.schroeder-usenix-html
weighted average ARR for drives under five yearsnot stated3.01percent of drives per yearAll seven data sets weighted by drive countARR is the annual replacement rate. A replacement is not a confirmed failure.schroeder-usenix-html
weighted average ARR without COM3not stated2.86percent of drives per yearSix data setsThe paper calls this 3.3 times 0.88%.schroeder-usenix-html
range of ARR by data set and drive type0.513.5percent of drives per yearDrives within the five-year nominal lifeOne COM3 group deployed in 1998 had 24% and is excluded by the paper.schroeder-usenix-html
HPC1 ARR over five yearsnot stated3.4percent of drives per yearHPC1: 765-node cluster collected August 2001 to May 2006The paper says this is significantly higher than the datasheet AFR of 0.88%.schroeder-usenix-html
weighted average ARR versus 0.88% datasheet AFRnot stated3.4timesAll seven data setsObservation 1 of the paper.schroeder-usenix-html
replacement rate versus datasheet in years 4 and 5710timesHPC1 within nominal lifeThe datasheet MTTF implies the rate in the denominator.schroeder-usenix-html
replacement rate versus datasheet for systems 5 to 8 years oldnot stated30timesOlder systems in the data setsPrinted as by as much as a factor of 30.schroeder-usenix-html
correlation of replacement counts in consecutive weeksnot stated0.72correlation coefficient (unitless)HPC1 onlyClose to 0 would be expected for a Poisson process.schroeder-usenix-html
correlation of replacement counts in consecutive monthsnot stated0.79correlation coefficient (unitless)HPC1 onlyClose to 0 would be expected for a Poisson process.schroeder-usenix-html
Weibull shape of time between replacementsnot stated0.71unitlessAll HPC1 nodesShape under 1 means a decreasing hazard rate. Compute nodes 0.73. File system nodes 0.76.schroeder-usenix-html
squared coefficient of variation of time between replacementsnot stated2.4unitlessHPC1An exponential distribution has a value of 1.schroeder-usenix-html
probability of two drives failing within 1 hour versus exponential modelnot stated4timesHPC1Real data versus the fitted exponential model.schroeder-usenix-html
probability of two drives failing within 10 hours versus exponential modelnot stated2timesHPC1Real data versus the fitted exponential model.schroeder-usenix-html
Google AFR from first year to three-year-old group1.78.6percent of drives per yearOver 100000 ATA drives 5400 to 7200 rpmPrinted as 1.7% in the first year to over 8.6% for 3-year-old drives. Age groups mix drive models.pinheiro-usenix-html
Backblaze quarterly AFR for Q2 2026not stated1.73percent of drives per year354415 drives and 31553350 drive days and 1498 failures from April to June 2026Backblaze's own inclusion rules. The opened page does not define a failure.backblaze-q2-2026
Backblaze lifetime AFR to June 30 2026not stated1.41percent of drives per year353041 drives and 558148607 drive days and 21609 failuresModels with more than 500 drives and more than 100000 lifetime drive days.backblaze-q2-2026

Columns

measure (string)
The quantity as the source names it.
value_low (number)
Reported lower value or bound, when supplied; empty means not stated. Read note for strictness, approximation and interpretation.
value_high (number)
Reported single value or upper bound, when supplied; empty means not stated. The note preserves qualifiers; this is not necessarily an exact value or confidence interval.
unit (string)
Unit stated in this row, applying to both reported-value columns.
scope (string)
Population and window the value applies to.
note (string)
What the value is not, or the source wording behind it.
citation_id (string)
Id of the opened source in the citations list.

License

Small derived table of figures printed in Schroeder and Gibson (FAST 2007), Pinheiro et al. (FAST 2007), and the Backblaze Q2 2026 Drive Stats post, with credit. Not a Creative Commons license. The USENIX proceedings page says rights to individual papers remain with the author or the author's employer. This file is not a copy of the papers, not the replacement logs, and not the Backblaze dataset. The Backblaze post asks that its raw Drive Stats data be cited and not resold, which this table does not redistribute.

Sources

  1. Disk failures in the real world: What does an MTTF of 1,000,000 hours mean to you?, Schroeder and Gibson, FAST 2007 (USENIX HTML proceedings) (accessed 2026-10-09)
  2. Disk Failures in the Real World, USENIX FAST 2007 abstract page (accessed 2026-10-09)
  3. Failure Trends in a Large Disk Drive Population, Pinheiro, Weber, and Barroso, FAST 2007 (USENIX HTML proceedings) (accessed 2026-10-09)
  4. Backblaze Drive Stats for Q2 2026, published September 29, 2026 (accessed 2026-10-09)

Published by Hesela team

Report a correction · Editorial standards · Reuse guidance

Cite this page
Hesela team. Disk replacement rates and fleet event gaps: reported values. Hesela. https://hesela.dev/datasets/mttf-vs-field-replacement-rates/